VELUX KFA 100 Smoke Detector Sensor
Installation
Smoke detector KFA 100 should always be fitted on the ceiling in accordance with current national legislation. After fitting the base, the smoke detector can be snapped into place. Position dust cover over the smoke detector until it is ready for operation.
Connection
The smoke detector is connected to the control system by means of a 2-core cable with a minimum cross-section of 0.5 mm2. This cable can be extended up to 100m. The terminal module in the control system must be moved to the last or only smoke detector. Note the colour of the cables in the terminal module when connecting. The terminal module in other smoke detectors must be removed. Up to ten smoke detectors can be connected to each control system. Smoke detectors KFA 100 must be installed in continuous single line connections to ensure that the complete line from the control system to the last detector is monitored. Star connection does not allow for monitoring.